Specifications
 |
 |
 |
 |
 |
 |
 |
|
Series |
SJ100 |
SJ300 |
L100 |
L300P |
|
Appearance |
|
|
|
|
|
Power
Source |
Rated
input voltage |
1-phase |
200-240 +5%/-10%,
50/60Hz +/-5% |
- |
200-240V +/-10%,
50/60Hz +/-5%
100-115V +/-10%,
50/60Hz +/-5% |
- |
|
2-phase
(200V) |
200-240V +10%/-10%,
50/60Hz +/-5% |
200-240V +/-10%,
50/60Hz |
200-240V +/-10%,
50/60Hz +/-5% |
200-240V +/-10%,
50/60Hz |
|
3-phase
(400V) |
380-460 +/-10%,
50/60Hz +/-5% |
380-480 +/-10%,
50/60Hz |
380-480 +/-10%,
50/60Hz +/-5% |
380-480 +/-10%,
50/60Hz |
|
Applicable
motor |
0.2-7.5kW |
0.4-55kW (75 to 150kW (available soon)) |
0.2-7.5kW |
11-55kW (75 to 132kW (available soon)) |
|
Output
frequency range |
0.5-360Hz |
0.1-400Hz |
0.5-360Hz |
0.1-400Hz |
|
Starting
torque |
200% or greater
(3.7kW and above: 180% or greater) |
200% or greater (at 0.5Hz)
150% at around 0Hz |
Around 100%
(Torque boost mode) |
100% or greater
(Torque boost mode) |
|
Continous
operting torque speed range |
6-60Hz (1:10) |
Up to 3.7kW: 6-60Hz (1:10)
5.5kW and above: 20-20Hz |
- |
- |
|
Braking
torque
|
Dynamic
brake(capacitor feedback) |
20-100% |
10-20% |
20-100% |
- |
|
DC
brake |
Performs under min.
frequency;
under set frequency |
Performs at start; under set frequency
at deceleration, or viaan external input |
Performs under min.
frequency;
under set frequency |
Performs at start; under set frequency
at deceleration, or viaan external input |
|
Overload
capacity |
150%, 60sec. |
150%, 60 sec., 200%, 0.5 sec. |
150%, 60sec. |
120%, 30 sec., 150% 0.5 sec. |
|
Acceleration/deceleration
time |
0.1-3,000sec. |
0.01-3,600sec. |
0.1-3,000sec. |
0.01-3,600sec. |
|
Multispeed
operation |
Max. 16-stage |
Max. 16-stage (bit command also available) |
Max. 16-stage |
Max. 16-stage (bit command also available) |
|
Analogue
input for frequency control |
0-10VDC, 4-20mA |
0-10Vdc, 4-20mA -10 to +10VDC, |
0-10VDC, 4-20mA |
0-10Vdc, 4-20mA -10 to +10VDC, |
|
Protective
functions |
Over-current
protection, overvoltage protection, undervoltage protection,
overload protection, temperature error CPU error, EEPROM error,
ground fault External trip PTC error, USP error, input overvoltage
protection, CT error |
Over-current protection, overload
protection, braking resistor overload protection, over-voltage
protection, EEPROM error, undervoltage error, CT error, CPU
error, external trip, USP error, ground fault, input overvoltage
protection, instantaneous power failure, option 1, 2 connection
error, inverter thermal trip, phase failure detection, IGBT
error, thermistor error |
Over-current
protection, overvoltage protection, undervoltage protection,
overload protection, temperature error CPU error, EEPROM error,
ground fault External trip input overvoltage protection, USP
error, PTC error |
Over-current protection, overload
protection, braking resistor overload protection, over-voltage
protection, EEPROM error, under-voltage error, CT error, CPU
error, external trip, USP error, ground fault, input over-voltage
protection, instantaneous power failure, option 1, 2 connection
error, inverter thermal trip, phase failure detection, lGBT
error, thermistor error |
|
Other
functions |
AVIR function,
curved acceleration/deceleration, frequency upper and lower
limit, fine adjustment of start frequency, carrier frequency
change, frequency jump, gain and bias setting, jogging, electronic
thermal level adjustment, retry, trip history, 2nd motor constants
setting, auto-tuning, fan on/off selection |
V/f free-setting (up to 5
points), frequency upper/lower limit, frequency jump, accelIdecel.
curve selection, manual torque boost value and frequency adjustment,
analog meter tuning, start frequency setting, carrier frequency
setting, electronic thermal free-setting output frequency
start/end setting, output frequency start/end ratio setting,
analog input selection, retry after trip, restart after trip,
retry after instantaneous power failure, various signal outputs,
reduced voltage soft start, overload restriction, default
value setting, deceleration and stop after power failure,
AVR function, fuzzy accel./decel.,auto-tuning(on-line/oftline),high-torque
multi-motor operation |
AVR function,
frequency upper/lower limit, PID control, carrier frequency
change, frequency jump, electronic thermal level adjustment,
fine adjustment of start frequency, gain/bias setting, retry,
automatic torque boost, trip history |
V/f free-setting (up to 5
points), frequency upper/lower limit, frequency jump, accel./decel.
curve selection, manual torque boost value and frequency adjustment,
analog meter tuning, starting frequency setting, carrier frequency
setting, electronic thermal free-setting output frequency
start/end setting, output frequency start/end ratio setting,
analog input selection, retry after trip, reduced voltage
soft start, overload restriction, automatic energy-saving |
|
Environmental
conditions |
Ambient
operating temperature |
-10 to 50 degrees C |
-10 to 50 degrees C |
-10 to 50 degrees C |
|
|
Humidity |
20 to 90%RH(no condensation) |
25 to 90%RH(no condensation) |
20 to 90%RH(no condensation) |
25 to 90%RH(no condensation) |
|
Location |
Less than 1,000m of
altitude, indoors (no corrosive gas not dust) |
Less than 1,000m of altitude, indoors
(no corrosive gas not dust) |
Less than 1,000m of
altitude, indoors (no corrosive gas not dust) |
Less than 1,000m of altitude, indoors
(no corrosive gas not dust) |
*See derating data in instruction manual when ambient operating temperature is 40 degrees C or over |